SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
479
2 Parameters
2.2 List of parameters
Procedure:
p4690 = set component number
p4691 = 1, 2, 30: Set the required procedure (save/download/delete).
p4691 = 9, 10, 36: Feedback signal on successful completion of the procedure.
p4691 = 11... 22, 37, 38: Error values if the procedure could not be executed successfully.
Value:
0:
Inactive
1:
Save SMI data
2:
Download SMI data
9:
SMI data downloaded and POWER ON required for component
10:
SMI data backup complete
11:
SMI data backup for selected component not found
12:
Selected component not available or not connected
13:
Insufficient memory space for backup
14:
Format of saved data is incompatible
15:
Transfer fault during data download
16:
Transfer fault during data backup
17:
Data backup does not match parameterized encoder/motor
18:
Data backup directory not permissible
19:
Component already contains data
20:
Component does not contain any data
21:
Component is not an SMI or a DQI
22:
SMI data cannot be downloaded for component
30:
Delete SMI data
35:
Confirmation of SMI data delete required
36:
SMI data deleted and POWER ON required for component
37:
Access level not sufficient for delete
38:
Delete SMI data not permitted for component
39:
SMI data for component cannot be deleted
Dependency:
Refer to: p4690, p4692, p4693
Notice:
Once SMI/DQI data has been deleted or downloaded successfully, the component has to be switched on (POWER
ON).
Note:
SMI: SINAMICS Sensor Module Integrated
DQI: DRIVE-CLiQ Sensor Integrated
Help for error value = 11:
- Save the data for the original SMI on the memory card.
- Use an SMI with a suitable hardware version.
Help for error value = 12:
- set the correct component number or connect the component.
Help for error value = 13:
- Use a memory card with more memory space.
Help for error value = 14:
- Create a data backup on the memory card corresponding to the SMI type.
Help for error value = 15:
- check the DRIVE-CLiQ wiring for the component.
Remedy for fault value = 16:
- check the DRIVE-CLiQ wiring for the component.
Help for error value = 17:
- Save the data for the original SMI on the memory card.
Help for error value = 18:
- set parameter p4693 to an appropriate value.
Help for error value = 19:
- Perform an SMI delete or use a blank SMI.
Help for error value = 20:
- Use an SMI that is not blank.
Help for error value = 21:
- set the correct component number (p4690).
Note for error value = 22:
- Data cannot be downloaded for component.