2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
266
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source for the scaling of the upper torque limit in p1522.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the scaling of the upper torque limit in p1522.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the scaling of the lower torque limit in p1523.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source for the scaling of the lower torque limit in p1523.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1528[0...n]
CI: Torque limit upper scaling / M_max upper scal
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
- - 1524[0]
p1528[0...n]
CI: Torque limit upper scaling / M_max upper scal
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
- - 2686[0]
p1529[0...n]
CI: Torque limit lower scaling / M_max lower scal
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
- - 1525[0]
p1529[0...n]
CI: Torque limit lower scaling / M_max lower scal
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
- - 2686[1]