SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
41
2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the status word of the closed-loop control.
Description:
Displays the actual speed setpoint at the input of the speed controller or U/f characteristic (after the interpolator).
Dependency:
Refer to: r0020
Note:
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
Description:
Displays the unsmoothed actual speed values sensed by the encoders.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Reserved
11
Frequency limit active
Yes
No
-
12
Current limiting controller voltage output
active
Yes
No
-
13
Current/torque limiting
Active
Inactive
6060
14
Vdc_max controller active
Yes
No
6220,
6320
15
Vdc_min controller active
Yes
No
6220,
6320
r0056.0...13
CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
PM250
PM260
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2526
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization completed
Yes
No
-
01
De-magnetizing completed
Yes
No
-
02
Pulse enable available
Yes
No
-
03
Soft starting present
Yes
No
-
04
Magnetizing completed
Yes
No
-
05
Voltage boost when starting
Active
Inactive
6301
06
Acceleration voltage
Active
Inactive
6301
07
Frequency negative
Yes
No
-
08
Field weakening active
Yes
No
-
09
Voltage limit active
Yes
No
6714
10
Slip limit active
Yes
No
6310
11
Frequency limit active
Yes
No
-
12
Current limiting controller voltage output
active
Yes
No
-
13
Current/torque limiting
Active
Inactive
6060
r0060
CO: Speed setpoint before the setpoint filter / n_set before filt.
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
2701, 6030, 6799
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r0061[0...2]
CO: Actual speed unsmoothed / n_act unsmoothed
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
4715
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]