SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
443
2 Parameters
2.2 List of parameters
Description:
Setting and connector output for a fixed percentage value.
Dependency:
Refer to: p2901, r2902, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling the main setpoint).
Description:
Setting and connector output for a fixed percentage value.
Dependency:
Refer to: p2900, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
Description:
Display and connector output for frequently used percentage values.
Index:
[0] = Fixed value +0 %
[1] = Fixed value +5 %
[2] = Fixed value +10 %
[3] = Fixed value +20 %
[4] = Fixed value +50 %
[5] = Fixed value +100 %
[6] = Fixed value +150 %
[7] = Fixed value +200 %
[8] = Fixed value -5 %
[9] = Fixed value -10 %
[10] = Fixed value -20 %
[11] = Fixed value -50 %
[12] = Fixed value -100 %
[13] = Fixed value -150 %
[14] = Fixed value -200 %
Dependency:
Refer to: p2900, p2901, p2930
Note:
The signal sources can, for example, be used to interconnect scalings.
Description:
Setting and connector output for a fixed torque value.
Dependency:
Refer to: p2900, p2901, r2902
p2900[0...n]
CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
1021
Min Max
Factory
setting
-10000.00 [%]
10000.00 [%]
0.00 [%]
p2901[0...n]
CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
1021
Min Max
Factory
setting
-10000.00 [%]
10000.00 [%]
0.00 [%]
r2902[0...14]
CO: Fixed values [%] / Fixed values [%]
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
1021
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2930[0...n]
CO: Fixed value M [Nm] / Fixed value M [Nm]
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2003
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
1021
Min Max
Factory
setting
-100000.00 [Nm]
100000.00 [Nm]
0.00 [Nm]