2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
424
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source for the feedback signal "fixed stop reached".
BI: p2637 = 1 signal
Fixed stop is reached.
BI: p2637 = 0 signal
Fixed stop is not reached.
Dependency:
Refer to: r2526, p2634
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The identification of "fixed stop reached" is, for the factory setting, dependent on the signal BO: r2526.4 (fixed stop
reached). This signal is influenced via p2634 (EPOS fixed stop, maximum following error).
Description:
Sets the signal source for the feedback signal "fixed stop outside the monitoring window".
BI: p2638 = 1 signal
Fixed stop is located outside the monitoring window.
BI: p2638 = 0 signal
Fixed stop is inside the monitoring window.
Dependency:
Refer to: r2526, p2635
Note:
The identification of "fixed stop outside the monitoring window" is, for the factory setting, dependent on signal BO:
r2526.5 (fixed stop outside window). This signal is influenced via p2635 (EPOS fixed stop monitoring window).
Description:
Sets the signal source for the feedback signal "torque limit reached" when traversing to fixed stop.
BI: p2639 = 1 signal
Torque limit is reached.
BI: p2639 = 0 signal
Torque limit is not reached.
Dependency:
Refer to: r1407
Note:
The feedback signal from "torque limit reached" is, for the factory setting, dependent on the signal BO: r1407.7
(torque limit reached).
p2637
BI: EPOS fixed stop reached / Fixed stop reached
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3616, 3617
Min Max
Factory
setting
- - 2526.4
p2638
BI: EPOS fixed stop outside the monitoring window / Fixed stop outside
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3616, 3617
Min Max
Factory
setting
- - 2526.5
p2639
BI: EPOS torque limit reached / M_limit reached
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3616
Min Max
Factory
setting
- - 1407.7