SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
585
2 Parameters
2.2 List of parameters
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
In addition to all of the combinations listed above, using bit 7, the "STO via Power Module terminals" function can be
enabled (this is permissible for r9771.19 = 1).
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change only becomes effective after a POWER ON.
STO: Safe Torque Off
Description:
Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 2.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
In addition to all of the combinations listed above, using bit 7, the "STO via Power Module terminals" function can be
enabled (this is permissible for r9771.19 = 1).
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change only becomes effective after a POWER ON.
STO: Safe Torque Off
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable STO via terminals (processor 2)
Enable
Inhibit
2810
02
Enable drive_integr motion_monitoring
functions (processor 2)
Enable
Inhibit
-
03
Enable PROFIsafe (processor 2)
Enable
Inhibit
-
07
Enable Power Module STO
Enable
Inhibit
-
p9801
SI enable functions integrated in the drive (processor 2) / SI enable fct P2
CU250S_V
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable STO via terminals (processor 2)
Enable
Inhibit
2810
02
Enable drive_integr motion_monitoring
functions (processor 2)
Enable
Inhibit
-
07
Enable Power Module STO
Enable
Inhibit
-