2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
320
List Manual, 09/2017, A5E33842890
Description:
The serial interface for the debug monitor is COM1 (commissioning interface, RS232) or COM2 (fieldbus interface,
RS485).
Value = 0: Deactivated
Value = 1: COM1, commissioning protocol is deactivated
Value = 2: COM2, field bus is deactivated
Value = 3: Reserved
Note:
Value = 2 is only possible for Control Units with RS485 as a field bus interface.
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
p2040 = 0:
Monitoring is deactivated.
Description:
Sets the PROFIBUS ident number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with ident number 3AA0 hex).
Value:
0:
SINAMICS
1:
VIK-NAMUR
Note:
Every change only becomes effective after a POWER ON.
Description:
Displays the PROFIdrive PZD state.
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p2039
Select debug monitor interface / Debug monit select
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 3 0
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
CU250S_V
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 [ms]
1999999 [ms]
100 [ms]
p2042
PROFIBUS Ident Number / PB ident No.
CU250S_V_DP
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0
r2043.0...2
BO: PROFIdrive PZD state / PD PZD state
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Setpoint failure
Yes
No
-
02
Fieldbus operation
Yes
No
-