2 Parameters
2.2 List of parameters
Description:
Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
AI: Analog Input
T: Terminal
Description:
Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
AI: Analog Input
T: Terminal
Description:
Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
p0756[0...1] = 2, 3 corresponds to a current input (r0752, p0757, p0759 are displayed in mA).
In addition, the associated DIP switch must be set.
For the voltage input, DIP switch AI0/1 must be set to "U".
For the current input, DIP switch AI0/1 or AI2 must be set to "I".
Value:
0:
Unipolar voltage input (0 V ... +10 V)
1:
Unipolar voltage input monitored (+2 V ... +10 V)
2:
Unipolar current input (0 mA ... +20 mA)
3:
Unipolar current input monitored (+4 mA to +20 mA)
4:
Bipolar voltage input (-10 V ... +10 V)
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Dependency:
Refer to: A03520
Warning:
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
If the system is operated when the load resistor is switched on (DIP switch set to "I"), the voltage between differential
inputs AI+ and AI- must not exceed 10 V or the injected 80 mA current otherwise the input will be damaged.
p0753[0...1]
CU analog inputs smoothing time constant / CU AI T_smooth
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
0.0 [ms]
1000.0 [ms]
0.0 [ms]
r0755[0...1]
CO: CU analog inputs actual value in percent / CU AI value in %
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
- [%]
- [%]
- [%]
p0756[0...1]
CU analog inputs type / CU AI type
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
0 4 [0]
4
[1] 4