2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
248
List Manual, 09/2017, A5E33842890
Description:
Sets the configuration for the closed-loop control and the motor model.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Display and BICO output for the control word of the speed controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Display and BICO output for the status word of the speed controller.
p1402[0...n]
Closed-loop current control and motor model configuration / I_ctrl config
Access level:
4
Calculated:
p0340 = 1,3
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
02
Current controller adaptation active
Yes
No
-
13
Current controller decoupling filter
Yes
No
-
r1406.4...15
CO/BO: Control word speed controller / STW n_ctrl
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2520
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
04
Hold speed controller I component
Yes
No
6040
05
Set speed controller I component
Yes
No
6040
08
Travel to fixed stop
Yes
No
8012
11
Droop enable
Yes
No
6030
12
Torque control active
Yes
No
6060
15
Set speed adaptation controller I
component
Yes
No
-
r1407.0...27
CO/BO: Status word speed controller / ZSW n_ctrl
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2522
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
U/f control active
Yes
No
-
01
Encoderless operation active
Yes
No
-
02
Torque control active
Yes
No
6030,
6060,
8011
03
Speed control active
Yes
No
6040
05
Speed controller I component frozen
Yes
No
6040
06
Speed controller I component set
Yes
No
6040
07
Torque limit reached
Yes
No
6060
08
Upper torque limit active
Yes
No
6060
09
Lower torque limit active
Yes
No
6060
10
Droop enabled
Yes
No
6030
11
Speed setpoint limited
Yes
No
6030
12
Ramp-function generator set
Yes
No
-
13
Encoderless operation due to a fault
Yes
No
-
14
I/f control active
Yes
No
-
15
Torque limit reached (without precontrol)
Yes
No
6060
16
Encoderless open-loop controlled operation
not active
Yes
No
-