2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
168
List Manual, 09/2017, A5E33842890
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency:
Refer to: p0860, r0863
Refer to: F07300
Note:
The monitoring function is disabled for the factory setting of p0860.
Description:
Display and BICO output for the status word and control word of the drive coupling.
Note:
For bit 01:
Bit 1 is used to control an external line contactor.
Description:
Sets the main contactor holding time after OFF1
Dependency:
Refer to: p0869
Note:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switching on inhibited must be
acknowledged via the source of p0840 = 0 (OFF1) – and before the main contactor holding time expires, should go
back to 1, otherwise the main contactor will open.
When operating a drive connected to SINUMERIK, which only closes the main contactor with the OFF1 command
(blocksize, chassis), p0867 should be set as a minimum to 50 ms.
Description:
Sets the configuration for the sequence control.
Dependency:
Refer to: p0867
p0861
Line contactor monitoring time / LineContact t_mon
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2634
Min Max
Factory
setting
0 [ms]
5000 [ms]
100 [ms]
r0863.0...1
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Closed-loop control operation
Yes
No
-
01
Energize contactor
Yes
No
2634
p0867
Power unit main contactor holding time after OFF1 / PU t_MC after OFF1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.0 [ms]
500.0 [ms]
50.0 [ms]
p0869
Sequence control configuration / Seq_ctrl config
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Keep main contactor closed for STO
Yes
No
-