Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 5 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description:
Sets the signal source for command 1 for the two-wire control/three-wire control.
Dependency:
Refer to: p0015, p3331, p3332, r3333, p3334
Note:
The mode of operation of this binector input is dependent on the wire control set in p0015.
Description:
Sets the signal source for command 2 for the two-wire control/three-wire control.
Dependency:
Refer to: p0015, p3330, p3332, r3333, p3334
Note:
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3328[0...n]
Fluid flow machine power point 5 / Fluid_mach P5
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 100.00
100.00
p3329[0...n]
Fluid flow machine speed point 5 / Fluid_mach n5
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 100.00
100.00
p3330[0...n]
BI: 2/3 wire control command 1 / 2/3 wire cmd 1
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2272, 2273
Min Max
Factory
setting
- - 0
p3331[0...n]
BI: 2/3 wire control command 2 / 2/3 wire cmd 2
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2272, 2273
Min Max
Factory
setting
- - 0