SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
151
2 Parameters
2.2 List of parameters
Description:
Sets the signal source to invert the analog output signals.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note:
AO: Analog Output
T: Terminal
Description:
Displays the status of analog outputs.
Note:
AO: Analog Output
Description:
Setting and connector output to control the analog outputs via fieldbus.
Index:
[0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency:
Refer to: p0771
Note:
AO: Analog Output
The following interconnections must be established to control the analog outputs via fieldbus:
- AO 0: p0771[0] with p0791[0]
- AO 1: p0771[1] with p0791[1]
p0782[0...1]
BI: CU analog outputs invert signal source / CU AO inv S_src
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9572
Min Max
Factory
setting
- - 0
r0785.0...1
BO: CU analog outputs status word / CU AO ZSW
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9572
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
AO 0 negative
Yes
No
-
01
AO 1 negative
Yes
No
-
p0791[0...1]
CO: Fieldbus analog outputs / Fieldbus AO
CU250S_V
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-200.000 [%]
200.000 [%]
0.000 [%]