2 Parameters
2.2 List of parameters
Note:
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
point p1464, then the controller below p1465 is adapted with p1461 or p1463. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
Description:
Sets the upper adaptation speed of the speed controller.
No adaptation is effective above this speed.
For the proportional gain, p1470 x p1461 is effective.
For the integral time, p1472 x p1463 is effective.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1460, p1461, p1462, p1463, p1464
Note:
If the upper transition point p1465 of the speed controller adaptation is set to lower values than the lower transition
point p1464, then the controller below p1465 is adapted with p1461 or p1463. This means that an adaptation can be
implemented for low speeds without having to change the controller parameters.
Description:
Sets the signal source for the scaling of the P gain of the speed controller.
This also makes the effective P gain (including adaptations) scalable.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the effective P gain of the speed controller.
Dependency:
The connector output signal r1468 is increased by a factor of 100 in order to improve the resolution.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Displays the effective integral time of the speed controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
p1465[0...n]
Speed controller adaptation speed upper / n_ctrl n upper
Access level:
3
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
6050
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
210000.00 [rpm]
p1466[0...n]
CI: Speed controller P-gain scaling / n_ctrl Kp scal
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
6050
Min Max
Factory
setting
- - 1
r1468
CO: Speed controller P-gain effective / n_ctr Kp eff
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6040
Min Max
Factory
setting
- - -
r1469
Speed controller integral time effective / n_ctr Tn eff
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
5040, 5042, 6040
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]