2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
526
List Manual, 09/2017, A5E33842890
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11...14] = Reserved
Description:
Displays mapped 32-bit transmit CANopen objects in the process data buffer.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11...14] = Reserved
Description:
Displays the currently effective CANopen operating mode.
To send the CANopen object 0x6061 mapped in a TPDO, this parameter can be correspondingly interconnected in
the PZD interface.
Description:
Display and connector output for the CANopen status word
r8761[0...14]
CAN mapped 32-bit transmit objects / TPDO 32 mapped
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r8762
CO: CAN operating mode display / Op mode display
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r8784
CO: CAN status word / Status word
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9226
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Ready for switching on
Yes
No
-
01
Ready
Yes
No
-
02
Operation enabled
Yes
No
-
03
Fault present
Yes
No
-
04
No coasting active
Yes
No
-
05
No Quick Stop active
Yes
No
-
06
Switching-on inhibited active
Yes
No
-
07
Alarm present
Yes
No
-
08
Can be freely interconnected (BI: p8785)
Yes
No
-
09
Control request
Yes
No
-