SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
375
2 Parameters
2.2 List of parameters
Description:
Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value exceeds this upper limit, this results in fault F07426.
Description:
Sets the lower limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value falls below this lower limit, this results in fault F07426.
Description:
Sets the scaling factor for the actual value of the technology controller.
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2271
Note:
For 100%, the actual value is not changed.
r2266
CO: Technology controller actual value after filter / Tec_ctr act aftFlt
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7958
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7958
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]
p2268
Technology controller lower limit actual value / Tec_ctrl l_lim act
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7958
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
-100.00 [%]
p2269
Technology controller gain actual value / Tech_ctrl gain act
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0.00 [%]
500.00 [%]
100.00 [%]