Function diagram
8
7
6
5
4
3
2
1
fp_9206_97_68.vsd
CANopen
G120 CU250S-2 CAN
05.09.2017
V4.7.9
Receive telegram, Predefined Connection Set (p8744 = 1)
<2>
Automatic assignment of the
RPDOs to the receive buffer.
The assignment is
made from RPDO 1,
RPDO 2 ... RPDO 8
and from receiver
buffer word.
Objects available a
multiple number of
times are
marshalled to the
same position in the
receive buffer.
Evaluation
of the
COB-ID
60400010
RPDO 1
Receive PDO 2
p8701
Mapping RPDO 2
p8711
Receive PDO 3
p8702
Mapping RPDO 3
p8712
Receive PDO 4
p8703
Mapping RPDO 4
p8713
Bit 15
r2090.15
PZD1 recv bitw
r2090
Bit 15
r2091.15
PZD2 recv bitw
r2091
Bit 15
r2092.15
PZD3 recv bitw
r2092
Bit 15
r2093.15
PZD4 recv bitw
r2093
r2050
PZD recv word
r2050
PZD recv word
r2050
PZD recv word
r2050
PZD recv word
r2050
PZD recv word
r2050
PZD recv word
r2050
PZD recv word
r2050
PZD recv word
<1>
Receive PDO 1
0000 hex ... 8000 06DF hex
p8700[0..1] (8000 06DF hex)
Mapping RPDO 1
0000 hex ... FFFF FFFF hex
p8710[0..3] (0000 hex)
RPDO 3
RPDO 4
60400010
RPDO 2
60420010
PZD receive word
Receive buffer
PZD receive word
PZD receive word
PZD receive word
PZD receive word
PZD receive word
PZD receive word
PZD receive word
1
2
3
4
5
6
7
8
.0
.0
.0
.0
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
Bit 0
...
Bit 0
...
Bit 0
...
Bit 0
...
To use automatic BICO interconnection (p8790 = 1), one of the receive words 1 - 4 must be used as control word 1 (STW1).
Telegram: up to 4 words or 64 bits. The sum of the various objects must not exceed 8 words.
RPDO: Receive Process Data Object
COB-ID: CAN object identification
<2>
<1>
COB-ID
Object
Object
Sub-D socket
CAN bus
CANopen
receive telegram
1
4