SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
349
2 Parameters
2.2 List of parameters
Description:
Displays the system runtime in days when the alarm was cleared.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125, r2134, r2145
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description:
Sets the signal source for the signal "ramp-function generator active" for the following signals/messages:
"Speed setpoint - actual value deviation within tolerance t_on" (BO: r2199.4)
"Ramp-up/ramp-down completed" (BO: r2199.5)
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The binector input is automatically interconnected to r1199.2 as a default setting.
Description:
Sets the configuration for messages and monitoring functions.
Dependency:
Refer to: r2197
Refer to: A07903
Note:
For bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
For bit 01:
When the bit is set, the load monitoring is only executed in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
For bit 03:
When the bit is set, r2197.1 and r2197.2 are determined using separate hysteresis functions.
For bit 05:
When this bit is set, a change to open-loop speed controlled operation is only possible when the motor is stationary.
r2146[0...63]
Alarm time removed in days / t_alarm res days
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8065
Min Max
Factory
setting
- - -
p2148[0...n]
BI: RFG active / RFG active
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
8011
Min Max
Factory
setting
- - 0
p2149[0...n]
Monitoring configuration / Monit config
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 1001 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Enable alarm A07903
Yes
No
8011
01
Load monitoring only in the 1st quadrant
Yes
No
8013
03
n_act > p2155 own hysteresis
Yes
No
8010
05
Stall monitoring for encoderless speed
control
Yes
No
-