2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
322
List Manual, 09/2017, A5E33842890
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
Notice:
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types. A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Description:
Selects the PZD (actual values) with word format to be sent to the fieldbus controller.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Selects the PZD (actual values) with word format to be sent to the fieldbus controller.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p2051[0...16]
CI: PROFIdrive PZD send word / PZD send word
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
U32 / Integer16
Can be changed:
U, T
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2450, 2470
Min Max
Factory
setting
- - [0]
2089[0]
[1] 63[0]
[2...16] 0
p2051[0...16]
CI: PROFIdrive PZD send word / PZD send word
CU250S_V
CU250S_V_CAN
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
U32 / Integer16
Can be changed:
U, T
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2450, 2470
Min Max
Factory
setting
- - 0