2 Parameters
2.2 List of parameters
Description:
Displays the error counter for the individual DRIVE-CLiQ connections/cables.
r9936[0]: sum of the error counter for all connections
r9936[1]: not used
r9936[2]: error counter for the feeder cable to DRIVE-CLiQ components with component number 2
...
r9936[199]: error counter for the feeder cable to DRIVE-CLiQ components with component number 199
The feeder cable is the DRIVE-CLiQ cable that is connected to a component in the direction of the Control Unit.
Dependency:
Refer to: p9937, p9938
Description:
Sets the configuration for the DRIVE-CLiQ diagnostics (error counter r9936).
Using this function, connections and cables of DRIVE-CLiQ connections can be checked for transfer errors. The error
counter is evaluated in the PHY blocks involved.
Dependency:
Refer to: r9936, p9938
Refer to: A01839
Note:
For bit 00:
To activate this function, p9938 must be set to 0 (inactive).
After changing the error counter (r9936), an appropriate alarm is output.
The alarm automatically disappears after 5 seconds.
For bit 08:
With p9937.8 = 1, the error counters are reset (r9936[0...199]).
After the reset, p9937.8 is automatically set to 0.
Description:
Sets the configuration for the DRIVE-CLiQ detailed diagnostics (r9943).
Using the detailed diagnostics, it is possible to investigate data transfer errors on an individual connection, selected
using p9942.
Value:
0:
Inactive
1:
Sum send and receive errors
2:
Only send errors
3:
Only receive errors
4:
Siemens internal
5:
Siemens internal
6:
Siemens internal
r9936[0...199]
DRIVE-CLiQ diagnostic error counter connection / DQdiag err counter
Access level:
4
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p9937
DRIVE-CLiQ diagnostic configuration / DQ diag config
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0000 0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Alarm for connection error
Yes
No
-
08
Reset error counter
Yes
No
-
p9938
DRIVE-CLiQ detailed diagnostics configuration / DQ diag config
Access level:
4
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 6 0