SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
527
2 Parameters
2.2 List of parameters
Note:
Corresponds to CANopen object 6041 hex.
For bit 10:
When the ramp-function generator is activated, the interconnection from CI: p2151 = r1119 can be changed, so that
to evaluate bit 10, the setpoint can be retrieved (taken) from in front of the ramp-function generator.
For bit 10, 12:
When braking, the two bits must indicate the same state. This is the reason that the following parameters must be set
the same:
p2161 (speed threshold value 3, for r2199.0) = p2163 (speed threshold value 4, for r2197.7)
p2150 (hysteresis speed 3, for r2199.0) = p2164 (hysteresis speed 4, for r2197.7)
Description:
Sets the signal source for bit 8 of the CANopen status word.
Dependency:
Refer to: r8784
Description:
Sets the signal source for bit 14 of the CANopen status word.
Dependency:
Refer to: r8784
Description:
Sets the signal source for bit 15 of the CANopen status word.
Dependency:
Refer to: r8784
Description:
Sets the automatic BICO interconnection of the CANopen control word.
Value:
0:
No interconnection
1:
Interconnection
Dependency:
Refer to: r2050, r2090, r2091, r2092, r2093, r8750, r8795
10
Target reached
Yes
No
-
11
Torque limit reached
Yes
No
-
12
Velocity equal to zero
Yes
No
-
14
Can be freely interconnected (BI: p8786)
Yes
No
-
15
Can be freely interconnected (BI: p8787)
Yes
No
-
p8785
BI: CAN status word bit 8 / Status word bit 8
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9226
Min Max
Factory
setting
- - 0
p8786
BI: CAN status word bit 14 / Status word bit 14
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9226
Min Max
Factory
setting
- - 0
p8787
BI: CAN status word bit 15 / Status word bit 15
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9226
Min Max
Factory
setting
- - 0
p8790
CAN control word - auto interconnection / STW interc auto
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0