2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
38
List Manual, 09/2017, A5E33842890
Notice:
p2080 is used to define the signal sources of the PROFIdrive status word interconnection.
Note:
For bit 03:
This signal is inverted if it is interconnected to a digital output.
For r0052:
The status bits have the following sources:
Bit 00: r0899 Bit 0
Bit 01: r0899 Bit 1
Bit 02: r0899 Bit 2
Bit 03: r2139 Bit 3 (or r1214.10 for p1210 > 0)
Bit 04: r0899 Bit 4
Bit 05: r0899 Bit 5
Bit 06: r0899 Bit 6
Bit 07: r2139 Bit 7
Bit 08: r2197 Bit 7
Bit 09: r0899 Bit 7
Bit 10: r2197 Bit 6
Bit 11: r0056 Bit 13 (negated)
Bit 12: r0899 Bit 12
Bit 13: r2135 Bit 14 (negated)
Bit 14: r2197 Bit 3
Bit 15: r2135 Bit 15 (negated)
Description:
Display and BICO output for status word 2.
Notice:
p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
05
Quick Stop active (OFF3)
No
Yes
-
06
Switching-on inhibited active
Yes
No
-
07
Alarm present
Yes
No
-
08
Deviation setpoint/actual speed
No
Yes
-
09
Control request
Yes
No
-
10
Maximum speed reached
Yes
No
-
11
I, M, P limit reached
No
Yes
-
12
Motor holding brake open
Yes
No
-
13
Alarm motor overtemperature
No
Yes
-
14
Motor rotates forwards
Yes
No
-
15
Alarm drive converter overload
No
Yes
-
r0053.0...11
CO/BO: Status word 2 / ZSW 2
Access level:
2
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DC braking active
Yes
No
-
01
|n_act| > p1226 (n_standstill)
Yes
No
-
02
|n_act| > p1080 (n_min)
Yes
No
-
03
I_act >= p2170
Yes
No
-
04
|n_act| > p2155
Yes
No
-
05
|n_act| <= p2155
Yes
No
-
06
|n_act| >= r1119 (n_set)
Yes
No
-
07
Vdc <= p2172
Yes
No
-
08
Vdc > p2172
Yes
No
-
09
Ramp-up/ramp-down completed
Yes
No
-
10
Technology controller output at the lower
limit
Yes
No
-
11
Technology controller output at the upper
limit
Yes
No
-