2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
678
List Manual, 09/2017, A5E33842890
Description:
Setting parameter for the run sequence of instance NCM 0 within the run-time group set in p20316.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source of input quantities X0 and X1 of instance NCM 1 of the numeric comparator.
Index:
[0] = Input X0
[1] = Input X1
Description:
Display parameter for binary quantity QU of instance NCM 1 of the numeric comparator.
QU is only set if X0 > X1.
Description:
Display parameter for binary quantity QE of instance NCM 1 of the numeric comparator.
QE is only set if X0 = X1.
p20317
NCM 0 run sequence / NCM 0 RunSeq
CU250S_V
(FBLOCKS)
CU250S_V_CAN
(FBLOCKS)
CU250S_V_DP
(FBLOCKS)
CU250S_V_PN
(FBLOCKS)
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7225
Min Max
Factory
setting
0 32000
820
p20318[0...1]
CI: NCM 1 inputs / NCM 1 inputs
CU250S_V
(FBLOCKS)
CU250S_V_CAN
(FBLOCKS)
CU250S_V_DP
(FBLOCKS)
CU250S_V_PN
(FBLOCKS)
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7225
Min Max
Factory
setting
- - 0
r20319
BO: NCM 1 output QU / NCM 1 output QU
CU250S_V
(FBLOCKS)
CU250S_V_CAN
(FBLOCKS)
CU250S_V_DP
(FBLOCKS)
CU250S_V_PN
(FBLOCKS)
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7225
Min Max
Factory
setting
- - -
r20320
BO: NCM 1 output QE / NCM 1 output QE
CU250S_V
(FBLOCKS)
CU250S_V_CAN
(FBLOCKS)
CU250S_V_DP
(FBLOCKS)
CU250S_V_PN
(FBLOCKS)
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7225
Min Max
Factory
setting
- - -