SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
265
2 Parameters
2.2 List of parameters
Danger:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Description:
Sets the scaling for the upper torque limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description:
Sets the scaling for the lower torque limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description:
Display and connector output for the upper torque limit of all torque limits without offset.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
Description:
Display and connector output for the lower torque limit of all torque limits without offset.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
p1524[0...n]
CO: Torque limit upper scaling / M_max upper scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
p1525[0...n]
CO: Torque limit lower scaling / M_max lower scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6630
Min Max
Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
r1526
CO: Torque limit upper without offset / M_max up w/o offs
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6060, 6630, 6640
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r1527
CO: Torque limit lower without offset / M_max low w/o offs
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6060, 6630, 6640
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]