SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
179
2 Parameters
2.2 List of parameters
Note:
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here. In a
long list, index 99 contains the parameter number at which position the list continues.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
Description:
Displays those parameters with a value other than the factory setting for this drive.
Dependency:
Refer to: r0990, r0991
Note:
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
Description:
Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
1:
Motorized potentiometer
2:
Analog setpoint
3:
Fixed speed setpoint
6:
Fieldbus
7:
Analog setpoint 2
10:
Motor potenti no main setpoint
11:
Motor potenti motor potentiometer
12:
Motor potenti analog setpoint
13:
Motor potenti fixed speed setpoint
16:
Motor potenti fieldbus
17:
Motor potenti analog setpoint 2
20:
Analog se no main setpoint
21:
Analog se motor potentiometer
22:
Analog se analog setpoint
23:
Analog se fixed speed setpoint
26:
Analog se fieldbus
27:
Analog se analog setpoint 2
30:
Fixed speed se no main setpoint
r0999[0...99]
List of modified parameters 10 / List chang par 10
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p1000[0...n]
Speed setpoint selection / n_set sel
CU250S_V_DP
CU250S_V_PN
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 200
[0]
6
[1] 0
[2] 0
[3] 0