2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
160
List Manual, 09/2017, A5E33842890
Description:
Displays the command data set (CDS) selected via the binector input.
Dependency:
Refer to: r0050, p0810, p0811
Note:
Command data sets are selected via binector input p0810 and following.
The currently effective command data set is displayed in r0050.
Description:
Displays the drive data set (DDS) selected via the binector input.
Dependency:
Refer to: r0051, p0820, p0821
Note:
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
Description:
Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p1055, p1056
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switching-on inhibited is acknowledged.
Only the signal source that originally switched on can also switch off again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
For drives with closed-loop speed control (p1300 = 20, 21), the following applies:
- BI: p0840 = 0 signal: OFF1 (braking with the ramp-function generator, then pulse suppression)
r0836.0...1
CO/BO: Command Data Set CDS selected / CDS selected
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8560
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
CDS selection bit 0
ON
OFF
-
01
CDS selection bit 1
ON
OFF
-
r0837.0...1
CO/BO: Drive Data Set DDS selected / DDS selected
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8565
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DDS selection bit 0
ON
OFF
-
01
DDS selection bit 1
ON
OFF
-
p0840[0...n]
BI: ON / OFF (OFF1) / ON / OFF (OFF1)
CU250S_V_DP
CU250S_V_PN
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2501, 2512
Min Max
Factory
setting
- - [0]
2090.0
[1] 0
[2] 0
[3] 0