2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
40
List Manual, 09/2017, A5E33842890
Description:
Display and BICO output for supplementary control word.
Note:
CDS: Command Data Set
DDS: Drive Data Set
The following control bits are displayed in r0055:
Bit 00: r1198.0
Bit 01: r1198.1
Bit 02: r1198.2
Bit 03: r1198.3
Bit 04: r0837.0
Bit 05: r0837.1
Bit 08: r2349.0 (negated)
Bit 09: r1239.11
Bit 11: r1406.11
Bit 12: r1406.12
Bit 13: r2138.13 (negated)
Bit 15: r0836.1
Description:
Display and BICO output for the status word of the closed-loop control.
r0055.0...15
CO/BO: Supplementary control word / Suppl STW
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2513
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed setpoint bit 0
Yes
No
-
01
Fixed setpoint bit 1
Yes
No
-
02
Fixed setpoint bit 2
Yes
No
-
03
Fixed setpoint bit 3
Yes
No
-
04
DDS selection bit 0
Yes
No
-
05
DDS selection bit 1
Yes
No
-
08
Technology controller enable
Yes
No
-
09
DC braking enable
Yes
No
-
11
Droop enable
Yes
No
-
12
Torque control active
Yes
No
-
13
External fault 1 (F07860)
No
Yes
-
15
CDS bit 1
Yes
No
-
r0056.0...15
CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
PM240
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2526
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Initialization completed
Yes
No
-
01
De-magnetizing completed
Yes
No
-
02
Pulse enable available
Yes
No
-
03
Soft starting present
Yes
No
-
04
Magnetizing completed
Yes
No
-
05
Voltage boost when starting
Active
Inactive
6301
06
Acceleration voltage
Active
Inactive
6301
07
Frequency negative
Yes
No
-
08
Field weakening active
Yes
No
-
09
Voltage limit active
Yes
No
6714
10
Slip limit active
Yes
No
6310