SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
369
2 Parameters
2.2 List of parameters
Description:
Displays the setpoint memory for the motorized potentiometer of the technology controller.
For p2230.0 = 1, the last setpoint that was saved is entered after ON.
Dependency:
Refer to: p2230
Description:
Sets the signal source to continually increase the setpoint for the motorized potentiometer of the technology
controller.
The setpoint change (CO: r2250) depends on the set ramp-up time (p2247) and the duration of the signal that is
present (BI: p2235).
Dependency:
Refer to: p2236
Description:
Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology controller.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency:
Refer to: p2235
Description:
Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency:
Refer to: p2238
r2231
Technology controller motorized potentiometer setpoint memory / Tec_ctrl mop mem
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7954
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2235[0...n]
BI: Technology controller motorized potentiometer raise setpoint / Tec_ctrl mop raise
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7954
Min Max
Factory
setting
- - 0
p2236[0...n]
BI: Technology controller motorized potentiometer lower setpoint /
Tec_ctrl mop lower
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7954
Min Max
Factory
setting
- - 0
p2237[0...n]
Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7954
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
100.00 [%]