SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
211
2 Parameters
2.2 List of parameters
Note:
For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (to the setpoint (r1170)) and stops the drive corresponding to the ramp-down time
(p1121 or p1135). While stopping via the ramp-function generator, STW1.4 is effective (enable ramp-function
generator).
Description:
Sets the signal source for speed setpoint 2 of the speed controller.
Dependency:
Refer to: p1155, r1170
Note:
For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (to the setpoint (r1170)) and stops the drive corresponding to the ramp-down time
(p1121 or p1135). While stopping via the ramp-function generator, STW1.4 is effective (enable ramp-function
generator).
When the function module "position control" (r0108.3 = 1) is activated, this connector input is interconnected as
follows as standard:
CI: p1160 = r2562
Description:
Displays the speed setpoint after the addition of the speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency:
Refer to: p1155, p1160
Note:
The value is only correctly displayed at r0899.2 = 1 (operation enabled).
Description:
Display and connector output for the speed setpoint after selecting the ramp-function generator.
The value is the sum of speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency:
Refer to: r1150, p1155, p1160
Description:
Displays the number of the selected fixed speed/velocity setpoint.
Dependency:
Refer to: p1020, p1021, p1022, p1023
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
p1160[0...n]
CI: Speed controller speed setpoint 2 / n_ctrl n_set 2
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3001, 3080
Min Max
Factory
setting
- - 2562[0]
r1169
CO: Speed controller speed setpoints 1 and 2 / n_ctrl n_set 1/2
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3080
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r1170
CO: Speed controller setpoint sum / Speed setpoint sum
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3001, 3080, 6300
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r1197
Fixed speed setpoint number actual / n_set_fixed No act
Access level:
4
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3010
Min Max
Factory
setting
- - -