2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
454
List Manual, 09/2017, A5E33842890
Description:
Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency:
Refer to: p0015, p3330, p3331, r3333, p3334
Note:
The mode of operation of this binector input is dependent on the wire control set in p0015.
Description:
Displays the control word for the two wire control/three wire control.
The control signals are dependent on the wire control set in p0015 and the signal states at the digital inputs.
Dependency:
Refer to: p0015, p3330, p3331, p3332, p3334
Description:
Sets the two wire control/three wire control.
Value:
0:
No wire control
1:
Two wire control clockwise/counterclockwise 1
2:
Two wire control clockwise/counterclockwise 2
3:
Three wire control enable clockwise/counterclockwise
4:
Three wire control enable ON/reversing
Dependency:
Refer to: p0015, p3330, p3331, p3332, r3333
Note:
This value depends on the wire control set in p0015.
Description:
Sets the signal source for the start of motion dependent on the sign of the setpoint.
Dependency:
Refer to: p3342, p3343, r3344
Refer to: A07352
p3332[0...n]
BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2273
Min Max
Factory
setting
- - 0
r3333.0...3
CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2272, 2273
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON
Yes
No
-
01
Reversing
Yes
No
-
02
ON inverted
Yes
No
-
03
Reversing inverted
Yes
No
-
p3334
2/3 wire control selection / 2/3 wire select
Access level:
4
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2272, 2273
Min Max
Factory
setting
0 4 0
p3340[0...n]
BI: Limit switch start / Lim switch start
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0