2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
26
List Manual, 09/2017, A5E33842890
Note:
A higher set access level also includes the lower one.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
Ready
1:
Quick commissioning
2:
Power unit commissioning
3:
Motor commissioning
4:
Encoder commissioning
5:
Technological application/units
11:
Function modules
15:
Data sets
17:
Basic positioner commissioning
25:
Position control commissioning
29:
Only Siemens internal
30:
Parameter reset
39:
Only Siemens internal
49:
Only Siemens internal
95:
Safety Integrated commissioning
Dependency:
Refer to: r3996
Note:
The drive can only be powered up outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description:
Runs the corresponding macro files.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
Macros available as standard are described in the technical documentation of the particular product.
p0010
Drive commissioning parameter filter / Drv comm. par_filt
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2800, 2818
Min Max
Factory
setting
0 95
1
p0015
Macro drive unit / Macro drv unit
CU250S_V_DP
CU250S_V_PN
Access level:
1
Calculated:
-
Data type:
Unsigned32
Can be changed:
C, C(1)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 999999
7