2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
292
List Manual, 09/2017, A5E33842890
Description:
Displays the switch-on stator frequency/ primary section frequency for the Lh adaptation for the induction motor
(ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the switch-on slip frequency for the Lh adaptation for the induction motor (ASM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Sets the integral time of the kT adaptation of the motor model for a permanent-magnet synchronous motor (PMSM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description:
Displays the corrective value of the kT adaptation of the motor model for a permanent-magnet synchronous motor
(PMSM).
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p0826, p1780
Note:
The display of the inactive data sets is only updated when changing over the data set.
Description:
Sets the pulse frequency for the converter.
This parameter is pre-set to the rated converter value when the drive is first commissioned.
Dependency:
Refer to: p0230
r1791
Motor model Lh adaptation switch-on frequency / MotMod Lh f_on
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
r1792
Motor model Lh adaptation switch-on slip / MotMod Lh fslip
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [Hz]
- [Hz]
- [Hz]
p1795[0...n]
Motor model kT adaptation integral time / MotMod kT Tn
Access level:
4
Calculated:
p0340 = 1,3,4
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6731
Min Max
Factory
setting
10 [ms]
10000 [ms]
100 [ms]
r1797[0...n]
Motor model kT adaptation corrective value / MotMod kT corr
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6731
Min Max
Factory
setting
- [Nm/A]
- [Nm/A]
- [Nm/A]
p1800[0...n]
Pulse frequency setpoint / Pulse freq setp
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8021
Min Max
Factory
setting
2.000 [kHz]
16.000 [kHz]
4.000 [kHz]