2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
462
List Manual, 09/2017, A5E33842890
Description:
Sets the ramp-up/ramp-down time of the ramp-up/ramp-down function generator to automatically record the friction
characteristic.
The drive is accelerated from standstill (setpoint = 0) up to the maximum speed/velocity (p1082) in this time.
Dependency:
Refer to: p3845
Description:
Sets the warm-up time.
For an automatic trace (record) to start, the highest selected speed (p3829) is approached and this time is held. After
this, the measurement is started with the highest speed.
Dependency:
Refer to: p3829, p3845
Description:
Compound braking current is used to define the amount of DC current that is produced on stopping the motor during
U/f operation to further increase the DC braking function.
Compound braking is a superimposition of the DC braking function with regenerative braking (net braking along the
ramp) after OFF1 or OFF3. This permits braking with controlled motor frequency and minimum power input into the
motor.
Effective braking without using additional hardware components is obtained by optimizing the ramp down time and
compound braking.
Dependency:
The compound braking current is only activated if the DC link voltage exceeds the threshold value in r1282.
Compound braking does not operate in the following cases:
- DC braking activated (p1230, r1239).
- motor is still not magnetized (e.g. for flying restart).
- vector control parameterized (p1300 >= 20).
- synchronous motor used (p0300 = 2xx).
Notice:
Generally, increasing the braking current improves the braking effect when stopping the motor. However, if the value
is set too high, then the drive can be tripped (shut down) as a result of overcurrent or ground fault.
Recommendation: p3856 < 100 % x (r0209 - r0331) / p0305 / 2
Compound braking generates a current in the motor with a ripple manifesting the rotational frequency. The higher the
braking current is set, the higher the resulting ripple, especially when the Vdc_max control is simultaneously active
(refer to p1280).
Note:
The parameter value is entered relative to the rated motor current (p0305).
Compound braking is deactivated with p3856 = 0%.
p3846[0...n]
Friction characteristic record ramp-up/ramp-down time / Frict rec t_RU/RD
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
7010
Min Max
Factory
setting
0.000 [s]
999999.000 [s]
10.000 [s]
p3847[0...n]
Friction characteristic record warm-up time / Frict rec t_warm
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
7010
Min Max
Factory
setting
0.000 [s]
3600.000 [s]
0.000 [s]
p3856[0...n]
Compound braking current / Compound I_brake
PM240
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 [%]
250.00 [%]
0.00 [%]