2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
438
List Manual, 09/2017, A5E33842890
Description:
Displays the corrective value for the position actual value.
Dependency:
Refer to: r2684
Note:
As standard, the following BICO interconnection is established: CI: p2513 = r2685
Using this value, e.g. modulo corrections are carried out.
Description:
Displays the effective torque limiting.
r2686[0]:
Displays the effective upper torque limiting when traversing to fixed stop (referred to CI: p1522, CI: p1523).
r2686[1]:
Displays the effective lower torque limiting when traversing to fixed stop (referred to CI: p1522, CI: p1523).
Index:
[0] = Upper
[1] = Lower
Dependency:
Refer to: p1520, p1521, p1522, p1523, r2676
Note:
As standard, the following BICO interconnections are established:
CI: p1528 = r2686[0]
CI: p1529 = r2686[1]
Description:
Displays the effective torque setpoint when reaching the fixed stop (referred to CI: p1522, CI: p1523).
Dependency:
Refer to: p1520, p1521, p1522, p1523, r2676
Description:
Sets the tolerance window for the position feedback signal. If, for a positioning operation, the actual value (r2521) lies
within this tolerance window of the target position, then the traversing block number is displayed at connector output
r2689.
r2685
CO: EPOS corrective value / Correction value
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
1
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3635
Min Max
Factory
setting
- [LU]
- [LU]
- [LU]
r2686[0...1]
CO: EPOS torque limiting effective / M_limit eff
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3616, 3617
Min Max
Factory
setting
- [%]
- [%]
- [%]
r2687
CO: EPOS torque setpoint / M_set
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3616, 3617
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
p2688
EPOS position feedback signal tolerance window / Pos_FS tol
CU250S_V (EPOS)
CU250S_V_CAN
(EPOS)
CU250S_V_DP
(EPOS)
CU250S_V_PN
(EPOS)
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [LU]
2147482647 [LU]
40 [LU]