2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
354
List Manual, 09/2017, A5E33842890
Description:
Sets the absolute current threshold for the messages.
"I_act >= I_threshold p2170" (BO: r2197.8)
"I_act < I_threshold p2170" (BO: r2198.8)
Dependency:
Refer to: p2171
Description:
Sets the delay time for the comparison of the current actual value (r0068) with the current threshold value (p2170).
Dependency:
Refer to: p2170
Description:
Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency:
Refer to: p2173
Description:
Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency:
Refer to: p2172
p2170[0...n]
Current threshold value / I_thres
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2002
Dyn. index:
DDS, p0180
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
8022
Min Max
Factory
setting
0.00 [Arms]
10000.00 [Arms]
0.00 [Arms]
p2171[0...n]
Current threshold value reached delay time / I_thresh rch t_del
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8022
Min Max
Factory
setting
0 [ms]
10000 [ms]
10 [ms]
p2172[0...n]
DC link voltage threshold value / Vdc thresh val
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2001
Dyn. index:
DDS, p0180
Unit group:
5_2
Unit selection:
p0505
Func. diagram:
-
Min Max
Factory
setting
0 [V]
2000 [V]
800 [V]
p2173[0...n]
DC link voltage comparison delay time / t_del Vdc
CU250S_V (Ext msg)
CU250S_V_CAN (Ext
msg)
CU250S_V_DP (Ext
msg)
CU250S_V_PN (Ext
msg)
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [ms]
10000 [ms]
10 [ms]