SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
93
2 Parameters
2.2 List of parameters
Description:
Sets the position and level of the alarm bit in the SSI protocol.
Notice:
The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note:
Value = dcba
ba: Position of the alarm bit in protocol (0 ... 63).
c: Level (0: Low level, 1: High level).
d: State of the evaluation (0: Off, 1: On).
Example:
p0435 = 1014
--> The evaluation is switched in and the alarm bit is at position 14 with a low level.
p0435 = 1114
--> The evaluation is switched in and the alarm bit is at position 14 with a high level.
Description:
Sets the position and parity of the parity bit in the SSI protocol.
Notice:
The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note:
Value = dcba
ba: Position of the parity bit in the protocol (0 ... 63).
c: Parity (0: even, 1: uneven).
d: State of the evaluation (0: Off, 1: On).
Example:
p0436 = 1015
--> The evaluation is switched in and the parity bit is at position 15 with even parity.
p0436 = 1115
--> The evaluation is switched in and the parity bit is at position 15 with uneven parity.
Description:
Sets the extended configuration of the Sensor Module.
p0435[0...n]
Encoder SSI alarm bit / Enc SSI alarm bit
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p0436[0...n]
Encoder SSI parity bit / Enc SSI parity bit
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p0437[0...n]
Sensor Module configuration extended / SM config ext
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0011 0000 0000 0000 0000 1000 0000
0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Data logger
Yes
No
-
01
Zero mark edge detection
Yes
No
-
02
Correction position actual value XIST1
Yes
No
-
04
Edge evaluation bit 0
Yes
No
-
05
Edge evaluation bit 1
Yes
No
-
06
Freeze the speed actual value for dn/dt
errors
Yes
No
-
07
Accumulate uncorrected encoder pulses
Yes
No
-
11
Fault handling after PROFIdrive
Yes
No
-