SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
513
2 Parameters
2.2 List of parameters
Description:
Sets the communication parameters for CANopen Receive Process Data Object 5 (RPDO 5).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1404 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the communication parameters for CANopen Receive Process Data Object 6 (RPDO 6).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1405 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the communication parameters for CANopen Receive Process Data Object 7 (RPDO 7).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Note:
Corresponds to the CANopen object 1406 hex.
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8704[0...1]
CAN Receive PDO 5 / Receive PDO 5
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
p8705[0...1]
CAN Receive PDO 6 / Receive PDO 6
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex
p8706[0...1]
CAN Receive PDO 7 / Receive PDO 7
CU250S_V_CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9204
Min Max
Factory
setting
0000 hex
8000 06DF hex
[0] 8000 06DF hex
[1] 00FE hex