SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
463
2 Parameters
2.2 List of parameters
Description:
Display and connector output for the status word of the compound braking and DC quantity control.
Dependency:
Refer to: p3856
Description:
Sets the configuration when operating a long stator motor.
Notice:
The following restrictions apply to this function:
- it is not permissible to change over the drive data set.
- the encoder/drive may not be parked using a PROFIBUS telegram.
- a maximum of 4 drives may be connected to the Control Unit.
- it is not permissible to commutate with the zero mark (p0404).
Note:
For bit 00:
All of the help functions for long stator motors can be enabled/disabled using this bit.
For bit 01:
When the bit is set, bit 14 (parking encoder active) is set to 0 in the encoder status word GX_ZSW independent of
whether the encoder is parked or not.
Description:
Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p15 and p1500 are
re-established and all of the dependent motor, open-loop and control-loop control parameters are calculated
(corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p15 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick parameterization (only) for BICO and motor parameters
3:
Quick parameterization for motor parameters (only)
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
r3859.0
CO/BO: Compound braking/DC quantity control status word / Comp-br/DC_ctr ZSW
PM240
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6797
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Compound braking active
Yes
No
-
p3870
Long stator configuration / Long stator config
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0000
bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Activate long stator help functions
Active
Inactive
-
01
Suppress Gx_ZSW.14
Active
Inactive
-
p3900
Completion of quick commissioning / Compl quick_comm
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 3 0