2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
146
List Manual, 09/2017, A5E33842890
Note:
When changing p0756, the parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten
with the following default values:
For p0756 = 0, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 1, p0757 is set to 2.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note:
The parameters for the characteristic do not have a limiting effect.
p0757[0...1]
CU analog inputs characteristic value x1 / CU AI char x1
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-50.000 160.000
0.000
p0758[0...1]
CU analog inputs characteristic value y1 / CU AI char y1
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
0.00 [%]
p0759[0...1]
CU analog inputs characteristic value x2 / CU AI char x2
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-50.000 160.000
10.000