2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
370
List Manual, 09/2017, A5E33842890
Description:
Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency:
Refer to: p2237
Description:
Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency:
Refer to: p2230
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency:
Refer to: r2250
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2248
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2238[0...n]
Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7954
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
-100.00 [%]
p2240[0...n]
Technology controller motorized potentiometer starting value / Tec_ctrl mop start
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7954
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
r2245
CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
PERCENT
Dyn. index:
-
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7954
Min Max
Factory
setting
- [%]
- [%]
- [%]
p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
7954
Min Max
Factory
setting
0.0 [s]
1000.0 [s]
10.0 [s]