SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
395
2 Parameters
2.2 List of parameters
Notice:
When speed precontrol is active (p2534 > 0 %), the following applies:
In addition to the set dead time (p2535), internally two position controller clock cycles are effective.
When speed precontrol is inactive (p2534 = 0 %), the following applies:
No dead time is effective (p2535 and internal).
Note:
Together with p2536, the timing behavior of the closed-loop control loop can be emulated.
Description:
Sets a PT1 filter to emulate the timing behavior of the closed-speed control loop.
Dependency:
Refer to: p2535
Notice:
When speed precontrol is inactive (p2534 = 0 %), the following applies:
If a PT1 filter has been set, it is not effective.
Note:
Together with p2535, the timing behavior of the closed-loop control loop can be emulated.
Description:
Sets the signal source for the adaptation of the proportional gain of the position controller.
Dependency:
Refer to: p2538
Description:
Sets the proportional gain (P gain, position loop gain, Kv factor) of the position controller.
Dependency:
Refer to: p2537, p2539, p2555, r2557, r2558
Note:
The proportional gain is used define at which traversing velocity which following error is obtained (without precontrol)
Low proportional gain:
Slow response to a setpoint - actual value difference, the following error becomes large.
High proportional gain:
Fast response to the setpoint - actual value difference, the following error becomes small.
p2536[0...n]
LR speed precontrol symmetrizing filter PT1 / n_prectrl filt PT1
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
4015
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
0.00 [ms]
p2537
CI: LR position controller adaptation / Adaptation
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4015
Min Max
Factory
setting
- - 1
p2538[0...n]
LR proportional gain / Kp
CU250S_V (Position
control)
CU250S_V_CAN
(Position control)
CU250S_V_DP
(Position control)
CU250S_V_PN
(Position control)
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
4015
Min Max
Factory
setting
0.000 [1000 rpm]
300.000 [1000 rpm]
1.000 [1000 rpm]