SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
175
2 Parameters
2.2 List of parameters
Description:
Displays the system runtime in ms since the last POWER ON.
Note:
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
Description:
The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
Value:
0:
Inactive
1:
Start a parameter reset
3:
Start download of volatile parameters from RAM
5:
Starts a safety parameter reset
10:
Start loading the parameters saved with p0971=10
11:
Start loading the parameters saved with p0971=11
12:
Start loading the parameters saved with p0971=12
30:
Start loading the delivery state saved with p0971=30
100:
Start a BICO interconnection reset
300:
Only Siemens internal
Dependency:
Refer to: F01659
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Peculiarities of communication via PROFIBUS DP:
- communication with Class 1 masters (e.g. S7 controllers) is interrupted.
- Communication with Class 2 masters (e.g. STARTER) is retained.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset is completed with p0970 = 0 and r3996[0] = 0.
For p0970 = 5 the following applies:
The password for Safety Integrated must be set.
When Safety Integrated is enabled, this can result in messages, which then require an acceptance test to be
performed.
Then save the parameters and carry out a POWER ON.
For p0970 = 1 the following applies:
If a Safety Integrated function is parameterized (p9601), then the safety parameters are not reset. In this case, a fault
(F01659) is output with fault value 2.
The following generally applies:
One index of parameters p2100, p2101, p2118, p2119, p2126, p2127 is not reset, if a parameterized message is
precisely active in this index.
p0969
System runtime relative / t_System relative
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8050, 8060
Min Max
Factory
setting
0 [ms]
4294967295 [ms]
0 [ms]
p0970
Reset drive parameters / Drive par reset
Access level:
1
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(1, 30)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 300
0