2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
268
List Manual, 09/2017, A5E33842890
Description:
Displays the minimum limit for the torque-generating current component.
Index 0 indicates the signal limited by the Vdc controller.
Index:
[0] = Limited
[1] = Unlimited
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description:
Display and connector output for the actual effective upper torque limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
The effective upper torque limit is reduced with respect to the selected upper torque limit p1520, if the current limit
p0640 is reduced or the rated magnetizing current of the induction motor p0320 is increased.
This may be the case for rotating measurements (see p1960).
The torque limit p1520 can be re-calculated using p0340 = 1, 3 or 5.
Description:
Display and connector output for the actual effective lower torque limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
The effective lower torque limit is reduced with respect to the selected lower torque limit p1521, if the current limit
p0640 is reduced or the rated magnetizing current of the induction motor p0320 is increased.
This may be the case for rotating measurements (see p1960).
The torque limit p1520 can be re-calculated using p0340 = 1, 3 or 5.
Description:
Sets the signal source to activate/deactivate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r1537[0...1]
Current limit minimum torque-generating current / Isq_min
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2002
Dyn. index:
-
Unit group:
6_2
Unit selection:
p0505
Func. diagram:
6640, 6710
Min Max
Factory
setting
- [Arms]
- [Arms]
- [Arms]
r1538
CO: Upper effective torque limit / M_max upper eff
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6020, 6640
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
r1539
CO: Lower effective torque limit / M_max lower eff
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2003
Dyn. index:
-
Unit group:
7_1
Unit selection:
p0505
Func. diagram:
6020, 6640
Min Max
Factory
setting
- [Nm]
- [Nm]
- [Nm]
p1545[0...n]
BI: Activates travel to a fixed stop / TfS activation
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2520, 3617, 8012
Min Max
Factory
setting
- - 0