SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
305
2 Parameters
2.2 List of parameters
Dependency:
Refer to: F07988
Note:
The encoder is only tested if the rotating measurement with encoder is selected (p1960 = 2).
The following parameters are influenced for the individual optimization steps:
Bit 00: None
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1460, p1462, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
Bit 05: p0391, p0392, p0393, p1402.2 only for induction motors
p1960 = 1, 3: p1458, p1459, p1470, p1472, p1496, p1400.0
p1960 = 2, 4: p1458, p1459, p1460, p1462, p1496, p1461, p1463
The identification of the q leakage inductance can only be carried out for unloaded motors or motors with a low load
(load approx. 30% below the rated motor torque). Only then is a current controller adaptation (p0391 ... p0393)
parameterized if the q-leakage inductance under no-load conditions is at least 30 % higher than the total leakage
inductance (p0356, p0358).
Description:
Sets the configuration of the rotating measurement.
Dependency:
Refer to: F07988
Note:
The encoder is only tested if the rotating measurement with encoder is selected (p1960 = 2).
The following parameters are influenced for the individual optimization steps:
Bit 00: None
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1460, p1462, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
Bit 05: p0391, p0392, p0393, p1402.2 only for induction motors
p1960 = 1, 3: p1458, p1459, p1470, p1472, p1496, p1400.0
p1960 = 2, 4: p1458, p1459, p1460, p1462, p1496, p1461, p1463
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Encoder test active
Yes
No
-
01
Saturation characteristic identification
Yes
No
-
02
Moment of inertia identification
Yes
No
-
03
Re-calculates the speed controller
parameters
Yes
No
-
04
Speed controller optimization (vibration test) Yes
No
-
11
Do not change the controller parameters
during the measurement
Yes
No
-
12
Measurement shortened
Yes
No
-
13
After measurement direct transition into
operation
Yes
No
-
p1959[0...n]
Rotating measurement configuration / Rot meas config
PM250
PM260
Access level:
3
Calculated:
p0340 = 1
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0001 1111 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Encoder test active
Yes
No
-
01
Saturation characteristic identification
Yes
No
-
02
Moment of inertia identification
Yes
No
-
03
Re-calculates the speed controller
parameters
Yes
No
-
04
Speed controller optimization (vibration test) Yes
No
-
11
Do not change the controller parameters
during the measurement
Yes
No
-