2 Parameters
2.2 List of parameters
SINAMICS G120 CU250S-2 Control Units
364
List Manual, 09/2017, A5E33842890
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 5 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 6 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 7 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Sets the value for fixed value 8 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2205[0...n]
CO: Technology controller fixed value 5 / Tec_ctr fix val 5
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7950
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
50.00 [%]
p2206[0...n]
CO: Technology controller fixed value 6 / Tec_ctr fix val 6
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7950
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
60.00 [%]
p2207[0...n]
CO: Technology controller fixed value 7 / Tec_ctr fix val 7
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7950
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
70.00 [%]
p2208[0...n]
CO: Technology controller fixed value 8 / Tec_ctr fix val 8
CU250S_V (Tech_ctrl)
CU250S_V_CAN
(Tech_ctrl)
CU250S_V_DP
(Tech_ctrl)
CU250S_V_PN
(Tech_ctrl)
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
DDS, p0180
Unit group:
9_1
Unit selection:
p0595
Func. diagram:
7950
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
80.00 [%]