Installation

Manual

Contents

- Installation

- Electrical connections

- How to order

Integrated system,  

CPU module with on-board 

display and I/O

model

 

vP4

22/04 - Code: ISTR_I_vP4_E_01_--

E

Installation

Wiring rules

Description

Plugs of all terminals

Flexible cable section:

Pitch 5 mm: 

0.2... 2.5 mm

²

 (AWG24... AWG12)

Pitch 3.5 mm: 

0.14... 1.5 mm

²

 (AWG28... AWG16)

L

Stripped wire

Screw:

 7mm

Flat blade  

screwdriver

Pitch 5 mm: 0.6 x 3.5 mm

Pitch 3.5 mm: 0.4 x 2.5 mm

Tightening  

torque

Pitch 5 mm: 0.5... 0.6 Nm

Pitch 3.5 mm: 0.22... 0.25 Nm

Technical data:

 - The green terminals are male connectors (pitch 3.5 or 5 mm), the correspond-

ent female connectors have screw or spring terminals for connecting the wires;

 - Made with self extinguishing material as required by UL94 V0 standard;

 - Overvoltage cathegory/pollution degree II/2;

 - Max. load current/section 8A/2.5mm² at 65°C;

 - Test pulse voltage: 4 kVp.

Make sure that the overall current absorption (modules and field devices) 

matches the power supply.

In order to avoid excessive voltage drops, install the most power consum-

ing modules closer to the power supply.

Suggested wires routing

Conduit f

or lo

w le

vel sensor cab

les

Conduit f

or supply and output cab

les

100

100

DO cables

Power cables

Comm.s cable

AI cables

Digital I/Os cables

100

100

A

Despite the fact that the instrument has been designed to work in an 

harsh and noisy environment, it is strongly recommended to follow 

the following suggestions.

All the wiring must comply with the local regulations.
Avoid to use electromagnetic contactors, power relays and high power motors nearby.
Avoid power units nearby, especially if controlled in phase angle.
Keep the low level sensor input wires away from power lines and output cables. 
Power lines and output cables must also be at 

100 mm

 (min.) away from the CPU. 

If this is not achievable, use shielded cables on the sensor inputs, with the shield 

connected to earth at only one side.

A

Warning! 

Whenever a failure or a malfunction of the device may cause dangerous 

situations for persons, things or animals, please remember that the plant 

must be equipped with additional devices which will guarantee safety.

Dimensions (mm)

142.00

86.00

50.71

38.60

Mounting position

-  Mount the CPU in a 75 x 130 mm 

hole;

-  In order to help the air ventilation 

flow, respect the distances between 

the CPUs and walls or other CPUs.

min. 60

43

min. 100

min. 80

Mounting position (mm)

Disposal

The appliance (or the 

product) must be 

disposed of separately in 

compliance with the local 

standards in force on 

waste disposal.

Mount and remove the CPU

1

 Open a 75 x 130 mm hole in the 

mounting panel;

2

 Insert the CPU into the hole until the 

frame rests on the panel;

3

 Mount the two red blocks and slide 

them until they are in contact with 

the panel and hold the CPU in place;

4

 To remove the CPU, sconnect the ter-

minals, then remove the red blocks 

and invert the mounting sequence.

&

"

Operating conditions

Environmental condition

B

Suggestion

Operating 
conditions

T

Temperature 

-20...+50°C

%Rh

Rh: 5... 95%  

non condensing

Special  
conditions

T

Temperature 

> 50°C

Use forced  
ventilation

%Rh

> 95% RH

Warm up

P

Conducting  
atmosphere

Use filter

Forbidden 

conditions

C

Corrosive  
atmosphere

E

Explosive 

atmosphere

- For indoor use only. 

- Max. usage altitude: 2000 m 

  on the sea level.

Summary of Contents for vP4

Page 1: ... local regulations Avoid to use electromagnetic contactors power relays and high power motors nearby Avoid power units nearby especially if controlled in phase angle Keep the low level sensor input wires away from power lines and output cables Power lines and output cables must also be at 100 mm min away from the CPU If this is not achievable use shielded cables on the sensor inputs with the shiel...

Page 2: ...24 V active outputs The current consumption of each output must not exceed 0 5 A and their cumulative output current must be less than 1 6 A whatever the feeding method m Warning Counter Inputs CNT1 and CNT2 are installed as an alternative to Digital Inputs DI7 and DI8 Terminals connections and plugs m Warning In the drawing and in the table that follow are listed and briefly described all the ter...

Page 3: ...NT2 Count Inputs DIG7 DIG7 CNT1 CNT1 DIG8 DIG8 CNT2 CNT2 X6 DI1 DI3 DI5 GND DI1 DI3 DI5 GND 24V DI2 DI4 DI6 24V DI2 DI4 DI6 In the drawing are connected the counter inputs as an example CNT1 and CNT2 Frequency meter input The channels can manage up to 10 kHz signals having a duty cycle that guarantees minimum of ON OFF signal of 20 ms Impulse counter input The minimum time of an impluse must be 20...

Page 4: ...3 PB USB X8 X2 X3 X5 DO1 DO3 DO5 DO7 GND GND DO2 DO4 DO6 DO8 X6 X4 RS485 GND AI1 AI2 AI3 PB USB X8 Load Load GND_AO 0 4 20 mA Analogue Outputs X4 GND_PWM GND_PWM AO PWM 2 AO PWM 2 AO PWM 1 AO PWM 1 GND_AO GND_AO ANALOG ANALOG PWM OUT PWM OUT Respect the polarity shown Resolution 14 bit Accuracy 0 1 In the drawing are connected only 2 outputs as an example OT3 and OT4 0 4 20 mA analogue output Type...

Reviews: