Freedom Sequence

Intelligent Power Manager

Owner’s Guide

Freedom Sequence with six AC relays 
PN: 809-0912 shown.

809-0912
809-0913

PNs:

FSequence IPM Owners Guide.book  Page i  Thursday, October 6, 2011  3:33 PM

Summary of Contents for Freedom Sequence

Page 1: ...Freedom Sequence Intelligent Power Manager Owner s Guide Freedom Sequence with six AC relays PN 809 0912 shown 809 0912 809 0913 PNs FSequence IPM Owners Guide book Page i Thursday October 6 2011 3 3...

Page 2: ...FSequence IPM Owners Guide book Page ii Thursday October 6 2011 3 33 PM...

Page 3: ...ALLY AGREED TO IN WRITING XANTREX TECHNOLOGY USA INC XANTREX A MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DO...

Page 4: ...f the Freedom Sequence Intelligent Power Manager The installer should have knowledge and experience in installing electrical equipment knowledge of the applicable installation codes and awareness of t...

Page 5: ...these instructions can damage the unit and or damage other equipment IMPORTANT These notes describe things which are important for you to know however they are not as serious as a danger warning or ca...

Page 6: ...nnected to the AC input output connections NOTE The power manager has no on off switch Circuits are always live when DC and AC input are present ELECTRICAL SHOCK HAZARD Do not expose the power manager...

Page 7: ...ons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance b...

Page 8: ...ined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the sepa...

Page 9: ...n 7 Circuit Status 9 Basic Configuration Settings 11 Advanced Settings 20 Circuit Level Advanced Settings 27 Freedom Sequence Operational Concepts 33 Freedom Sequence SCP Menu Map 40 Specifications 41...

Page 10: ...FSequence IPM Owners Guide book Page ii Thursday October 6 2011 3 33 PM...

Page 11: ...xiliary connector port which can control external DC circuits based on Battery Voltage These four DC relays can also be used to control external AC circuits2 Circuit level override from load shed3 and...

Page 12: ...iary connector wiring harness AC wiring terminal covers and Xanbus terminator NOTE Keep the carton and packing material in case you need to return the power manager for servicing Xanbus terminator DC...

Page 13: ...verter Charger the power manager provides advanced power optimization features of interactive charger de rating and automatic inverter assist to provide additional power to support high peak power dem...

Page 14: ...ct works on a Xanbus network Xanbus enabled products are Simple to operate and routine tasks are automated Controlled by software that eliminates analog signalling errors Less susceptible to interfere...

Page 15: ...S and Freedom SW 4 DC auxiliary connector port contains the terminals for four DC relays B signal and DC power to the Freedom Sequence 5 AC relay three wire terminal blocks provide six or four Cage Cl...

Page 16: ...ECT XANBUS DC DISCONNECT 50A 300A 300A A A NOTE The Freedom Sequence power manager must be permanently installed by a qualified installer in a controlled environment Figure 3 shows a simple configurat...

Page 17: ...In the example below the Freedom Sequence power manager is designated as FSPM 00 Figure 4 Xanbus System Control Panel SCP System Status Xanbus System Control Panel SCP FGA 809 0921 AC In Charge Invert...

Page 18: ...CP Clock menu Complete list of device specific status information including basic configuration and advanced settings for the Freedom Sequence To view the Freedom Sequence s Device Status press the En...

Page 19: ...10 DCLoad4 10 Last Shed Current On 3 0A 4 0A On N A N A On N A N A On N A N A On N A N A Enter Func FSPM 00 Circuit Status 4 Last She Current 5 ACLoad5 5 Last Shed Current Cont 2 0A On 3 7A 1 0A First...

Page 20: ...tly enabled ON or not Off 3 This number corresponds to the AC circuit ID label found on the product like AC 1 is 1 AC 2 is 2 et cetera 7 to 10a refer to the four DC relays a 5 to 8 for the Freedom Seq...

Page 21: ...ircuit Status Config On 0 0A 12 8V FSPM 00 Config Mode SHR BKR Mode SHR BKR Rating Circuit Config Operating Auto 30 0A FSPM 00 Config Mode SHR BKR Mode SHR BKR Rating Circuit Config Restore Defaults O...

Page 22: ...10 Load Shed 6 Enabled 7 Enabled 8 Enabled 9 Enabled 10 Enabled Enter Func FSPM 00 Config Mode SHR BKR Mode SHR BKR Rating Circuit Config Operating Auto 30 0A Complete list of circuit configuration i...

Page 23: ...ettings1 When Freedom Sequence is first powered up it will start operation in Operating mode To change the Mode from the Device Status screen 1 OEM default settings the OEM Profile are programmed by t...

Page 24: ...Manual the shore breaker rating can be modified and set between 5 to 50 amps By default the setting for Shore Breaker Mode is Auto To change the shore breaker mode from the Device Status screen FSPM 0...

Page 25: ...mp limit and Line2 as well If it detects a single phase AC line and the shore breaker rating is set to 30 amps Freedom Sequence will apply a combined 30 amp limit to loads connected with Line1and Line...

Page 26: ...automatically get copied to the User profile If by mistake a wrong setting is configured all basic and advanced settings can be restored to their OEM settings via Restore Defaults from the Config scre...

Page 27: ...ad demand exceeds the shore or generator breaker capacity See AC Load Shedding on page 34 for more information A priority of 1 is equivalent to the highest priority therefore it is the last to be shed...

Page 28: ...organize the priority numbers for the rest of the relays To change the priority setting from the Device Status screen 1 For the four circuit Freedom Sequence model AC circuits are ACLoad1 up to ACLoa...

Page 29: ...bled since this is not done automatically By default the Load Shed setting of all the AC and DC relays is set to Enabled To change the Load Shed from the Device Status screen FSPM 00 Status L2 Amps Ba...

Page 30: ...the ones found in Advanced Settings Changes in your power manager s settings can affect the power management of your controlled appliances A professional installer at your dealership possesses the ex...

Page 31: ...onfig 0 0A 12 8V Enter Func Enter Func FSPM 00 Status Batt Voltage Circuit Status Config Advanced Settings 12 8V FSPM 00 Advanced Settings BKR Derating GEN BKR Rating GEN Warmup Delay Connect Seq Dela...

Page 32: ...Shedding on page 34 To change the breaker derating from the Advanced Settings screen IMPORTANT Appliances and circuit breakers that are 100 rated will have a listing on their product label similar to...

Page 33: ...device s user guide under its specifications or contact the manufacturer for information on the timer rating Choose a delay that is highest between these two devices To change the generator warmup del...

Page 34: ...an overload condition is detected Freedom Sequence will wait for two seconds before disconnecting the load circuit controlled through that relay To change the Connect Seq Delay from the Advanced Sett...

Page 35: ...me AC load circuit gets reconnected somehow The inverter charger can either accept this request and disqualify its incoming AC or reject the request and keep drawing AC current For more information se...

Page 36: ...from the Advanced Settings screen FSPM 00 Status L2 Amps Batt Voltage Circuit Status Config 0 0A 12 8V FSPM 00 Status Batt Voltage Circuit Status Config Advanced Settings 12 8V FSPM 00 Advanced Setti...

Page 37: ...gs 10sec 2 Connect Seq Delay AC Disq Priority Circuit1 Circuit2 FSPM 00 Circuit 2 ACLoad2 Enabled ACInputOut Line1 Circuit Name Load Shed Circuit Type AC Line Complete list of circuit level advanced s...

Page 38: ...oad Shed page 30 Circuit Type page 30 AC Line page 30 Priority page 31 Reconnect MRGN page 32 DC Relay Settings The Freedom Sequence has DC relays2 which can be used to connect and disconnect DC loads...

Page 39: ...Mode is set to Standby 1 Circuit names can be up to ten characters long Valid characters are from a to z A to Z 0 to 9 symbols forward slash and hyphen Spaces underscore and period are not accepted s...

Page 40: ...ings are shown below DC Relays When the type of load circuit is changed from DC to AC the line association can either be Line1 or Line2 Default settings are shown below NOTE DC relays can be used to c...

Page 41: ...connected during the GEN Soft Start process After the Generator Run B signal goes high Freedom Sequence will apply the Gen Warmup Delay At the end of this Gen Warmup Delay the Freedom Sequence power m...

Page 42: ...the factory setting of Reconnect MGN for all AC relays is set to 10 Battery Voltage Triggers The Freedom Sequence has four DC relays which can be used to connect and disconnect DC loads on the system...

Page 43: ...when 240 volts is measured between Line1and Line2 and that the voltages are found out of phase by more than 100 degrees Loading of Shore Generator Breaker Ratings The Freedom Sequence has the ability...

Page 44: ...ough to correct the overload condition the power manager will continue to shed the next lowest priority ranking load that is On until the overload condition is corrected The Freedom Sequence power man...

Page 45: ...ig FSPM Advanced Settings 2 Ph Shore1 25 0A 15 0A 12 0V On 10 0A On 15 0A Off 0 0A On 6 0A On 4 0A On 5 0A On 0 0A On 0 0A On 0 0A On 0 0A STATUS AT OVERLOAD PRESENT CONFIGURATION LINE1 L1 LINE2 L2 ST...

Page 46: ...e DC relays has a N O and N C contact point which will toggle to Closed and Open positions respectively when a DC relay is triggered Using DC Relay to control AC load circuits The DC Relays can also b...

Page 47: ...g screen of the SCP Circuit Priority on page 17 or through the Circuit Level Advanced Settings screen Priority on page 31 The power manager adjusts the priority settings for the rest of the circuits a...

Page 48: ...ows the user the flexibility to force an AC load to turn On for just a few minutes without the need to change the priority order of all AC load circuits When an AC load circuit s Load Shed setting is...

Page 49: ...bypass loads However if the inverter charger is a Xanbus enabled device and is programmed to support Freedom Sequence then the current draw by the charger can be regulated to assist in optimizing the...

Page 50: ...ing GEN BKR Rating GEN Warmup Delay Connect Seq Delay AC Disq Priority Nom DC Voltage Circuit1 Circuit2 Circuit3 Circuit4 Circuit5 Circuit6 Circuit7 Circuit8 Circuit9 Circuit10 Enabled 30 0A 0sec 10se...

Page 51: ...nnector port 4 3 pin connector for each DC relay 1 2 pin connector for one B signal 1 2 pin connector for battery Environmental Specifications Operating range 20 to 50 C 4 to 122 F Electrical Specific...

Page 52: ...to use parts or products of original or improved design in the repair or replacement If Xantrex repairs or replaces a product its warranty continues for the remaining portion of the original Warranty...

Page 53: ...stems This warranty does not apply to and Xantrex will not be responsible for any defect in or damage to a the product if it has been misused neglected improperly installed physically damaged or alter...

Page 54: ...OF ANY KIND EVEN IF XANTREX HAS BEEN ADVISED OR HAD REASON TO KNOW OF THE POSSIBILITY OF SUCH DAMAGE B ANY LIABILITY ARISING IN TORT WHETHER OR NOT ARISING OUT OF XANTREX S NEGLIGENCE AND ALL LOSSES...

Page 55: ...hone number where you can be reached during work hours A brief description of the problem Ship the unit prepaid to the address provided by your Xantrex customer service representative If you are retur...

Page 56: ...___________________ Purchase Date ______________________ Type of installation e g RV truck ______________________ Length of time unit has been installed ______________________ Battery battery bank siz...

Page 57: ...FSequence IPM Owners Guide book Page i Thursday October 6 2011 3 33 PM...