26
Freedom Sequence Intelligent Power Manager Owner’s Guide
Advanced Settings
DC Voltage Setting
The Freedom Sequence power manager can be used with a 12-volt or
24-volt battery system. Depending on which battery system is used, the
power manager can be set correspondingly to either
12.0V
or
24.0V
.
All four DC relays will have default settings for each battery trigger set/
clear values based on the selected value of the DC Voltage setting. See
“Battery Voltage Triggers” on page 32.
By default, the factory setting is set to
12.0 V
.
NOTE
: This setting can only be modified when
Mode
is set to
Standby
.
To change the DC voltage setting from the
Advanced Settings
screen:
FSPM 00: Status
L2 Amps
Batt Voltage
Circuit Status
Config
0.0A
12.8V
FSPM 00: Status
Batt Voltage
Circuit Status
Config
Advanced Settings
12.8V
FSPM 00: Advanced Settings
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
Nom DC Voltage
[30.0A]
[2sec]
[5sec]
[12.0V]
FSPM 00: Advanced Settings
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
Nom DC Voltage
[30.0A]
[2sec]
[5sec]
[*12.0V]
FSPM 00: Advanced Settings
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
Nom DC Voltage
[30.0A]
[2sec]
[5sec]
[24.0V]
1
Press all three buttons to
enable Advanced Settings.
2
Scroll down to select
Advanced Settings.
5
Press to change
the setting.
6
Scroll up or down
to choose a value.
3
Press button.
7
Press to
confirm the
selected
value.
4
Scroll down
FSequence IPM Owners Guide.book Page 26 Thursday, October 6, 2011 3:33 PM