Chapter 1: Installation and Initial Configuration
24
PMB Branch Circuit Wiring
A
CT plugs into 2-pin locking connector
(Molex 43640-0201)
B
Branch Circuits have two labels: Red
labels for odd/even numbered panels.
White labels for sequentially
numbered panels.
C
Multi-conductor CT cable. Available
lengths: 3m, 10m.
D
Connect labeled end into matching
labeled connector
All CTs 333mV output. DO NOT use
current output CT.
CT can be connected to live circuit in
either direction. Meter auto corrects
polarity.
Branch Circuit
Description
Current Transformers
How
Many
Connect To
Line-Neutral (LN)
120V/230V circuit wired to 1-pole circuit breaker
1
phase line
Line-Line (LL)
208/240/400V circuit wired to 2-pole circuit breaker
1
either phase
line
Line-Line-Neutral
(LLN)
120V+208/240V circuit wired to 2-pole circuit breaker 2
each phase line
Three-Phase (LLL,
LLLN)
3-phase circuit wired to 3-pole circuit breaker
3
each phase line
Содержание PMC-1000
Страница 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Страница 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Страница 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Страница 76: ...Chapter 2 Connecting External Equipment Optional 64...
Страница 123: ...Chapter 3 Using the Web Interface 111...
Страница 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Страница 559: ...Appendix D RADIUS Configuration Illustration 547 10 Select Standard to the left of the dialog and then click Add...
Страница 560: ...Appendix D RADIUS Configuration Illustration 548 11 Select Filter Id from the list of attributes and click Add...
Страница 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Страница 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Страница 594: ...Appendix E Additional BCM2 Information 582...
Страница 612: ......