Chapter 2: Connecting External Equipment (Optional)
51
DPX-ENVHUB4 sensor hub
DPX sensor packages
Using an Optional DPX-ENVHUB2 cable
A Raritan
DPX-ENVHUB2 cable doubles the number of connected
environmental sensors per SENSOR port.
This cable supports DPX sensor packages only. Do NOT connect DPX2,
DPX3 or DX sensor packages to it.
To connect DPX sensor packages via the DPX-ENVHUB2 cable:
1.
Use an RJ-12 to RJ-45 adapter to connect the DPX-ENVHUB2 cable
to the BCM2.
a.
Connect the adapter's RJ-12 connector to the cable.
b.
Connect the adapter's RJ-45 connector to the RJ-45 SENSOR
port on the BCM2.
2.
The cable has two RJ-12 sensor ports. Connect DPX sensor
packages to the cable's sensor ports.
3.
Repeat the above steps if there are additional SENSOR ports on your
BCM2.
Содержание PMC-1000
Страница 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Страница 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Страница 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Страница 76: ...Chapter 2 Connecting External Equipment Optional 64...
Страница 123: ...Chapter 3 Using the Web Interface 111...
Страница 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Страница 559: ...Appendix D RADIUS Configuration Illustration 547 10 Select Standard to the left of the dialog and then click Add...
Страница 560: ...Appendix D RADIUS Configuration Illustration 548 11 Select Filter Id from the list of attributes and click Add...
Страница 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Страница 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Страница 594: ...Appendix E Additional BCM2 Information 582...
Страница 612: ......