Chapter 2: Connecting External Equipment (Optional)
59
Connecting a DPX2 Sensor Package to DX
You can connect only one DPX2 sensor package to the "end" of a DX
sensor chain. It is strongly recommended to use an RJ-12 to RJ-45
adapter for connecting the DPX2 to the final DX in the chain.
The maximum number of DX sensor packages in the chain must be less
than 12 when a DPX2 sensor package is involved.
When connecting a DPX2 sensor package containing three DPX2
sensors:
A maximum of nine DX sensor packages can be cascaded because
12-3=9.
When connecting a DPX2 sensor package containing two DPX2
sensors:
A maximum of ten DX sensor packages can be cascaded because
12-2=10.
When connecting a DPX2 sensor package containing one DPX2
sensor:
A maximum of eleven DX sensor packages can be cascaded because
12-1=11.
Содержание PMC-1000
Страница 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Страница 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Страница 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Страница 76: ...Chapter 2 Connecting External Equipment Optional 64...
Страница 123: ...Chapter 3 Using the Web Interface 111...
Страница 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Страница 559: ...Appendix D RADIUS Configuration Illustration 547 10 Select Standard to the left of the dialog and then click Add...
Страница 560: ...Appendix D RADIUS Configuration Illustration 548 11 Select Filter Id from the list of attributes and click Add...
Страница 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Страница 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Страница 594: ...Appendix E Additional BCM2 Information 582...
Страница 612: ......